Fundamentals

Sizing a compressed-air buffer (storage) receiver

A buffer receiver stores compressed air to ride through a short demand peak without collapsing network pressure. Its volume is found directly from four inputs: the peak flow, the compressor’s make-up during the peak, the duration, and the pressure drop you can tolerate:

V = (Q_net × t × P_atm) / (60 × ΔP)        with   Q_net = Q_demand − Q_makeup
SymbolMeaningUnit
VRequired receiver volumeft³
Q_netNet flow the receiver must supply (demand − make-up)SCFM
tPeak durations
P_atmReference atmospheric pressure ≈ 14.5 psia (1 bar, SCFM reference)psia
ΔPAllowable pressure drop = start pressure − lowest tolerable pressurepsi

When do you need a buffer receiver?

The compressor is sized on the average demand; the receiver absorbs the peaks. As soon as a station draws far more than the available capacity for a few seconds (blow-off, long-stroke cylinder, leak test, line start-up), the air must come from a reserve or pressure sags. The receiver decouples supply from demand: it “shaves” the peak and lets the compressor run smoothly.

Net flow: don’t forget the compressor’s make-up

During the peak the compressor doesn’t stop: it keeps feeding the network. So the receiver only has to make up the difference between what the event demands and what the compressor already supplies.

  • If make-up ≥ demand, the compressor keeps up on its own: no buffer receiver is needed for that event.
  • Otherwise, size on Q_net = Q_demand − Q_makeup. Ignoring make-up gives a needlessly large receiver.

Worked example

A blow-off station draws 100 SCFM for 20 seconds. The compressor supplies 30 SCFM during that time. Pressure starts at 110 psig and must not fall below 95 psig (ΔP = 15 psi).

  • Net flow: Q_net = 100 − 30 = 70 SCFM
  • V = (70 × 20 × 14.5) / (60 × 15) = 22.6 ft³, i.e. ≈ 169 US gallons (0.64 m³)

So you would pick a dedicated receiver of at least 200 gallons near the station. Ignoring make-up, you would have sized on 100 SCFM (≈ 242 gal), over 40 % too big.

ΔP is the decisive lever. Volume is inversely proportional to ΔP: if the equipment tolerates only a 5 psi drop (110 → 105) instead of 15, the required receiver triples. The first question to the process is therefore: what is the lowest acceptable pressure?

Local receiver or central receiver

A large central receiver smooths the whole plant; a receiver dedicated to the demanding station (as close to the peak as possible, with its own feed) is often more effective for an isolated, one-off demand. Placement relative to the dryer also matters: see Air receiver: before or after the dryer?.

Flow is reasoned in SCFM; to avoid confusing it with ACFM or standardised units, see Flow units.

With the Onyx M3 tools

  • Calculator: Receiver storage, enter the event flow, the compressor make-up, the duration and the two pressures: it computes the net flow and the required volume (gal, ft³, m³).
  • Calculator: Metered recovery, goes further: it checks that a given receiver rides through the peak and recharges in time before the next one.

References

  • CAGI, Compressed Air & Gas Handbook, Chapter 4 “Compressed Air System Design”: storage and demand management
  • Compressed Air Challenge, Best Practices for Compressed Air Systems: storage sizing and peak shaving
  • ISO 1217 / CAGI: SCFM reference (1 bar absolute, 20 °C) used as P_atm in the formula

Frequently asked questions

What is a buffer (storage) receiver for?

A buffer receiver stores compressed air to absorb short demand peaks (a blow-off burst, a large cylinder, a tool change) without dropping network pressure or forcing the compressor to react instantly. It decouples supply from demand: the compressor covers the average, the receiver covers the peak.

What is the formula for a buffer receiver volume?

V = (Q_net × t × P_atm) / (60 × ΔP), where Q_net is the net flow in SCFM (event demand minus compressor make-up during the event), t the event duration in seconds, P_atm ≈ 14.5 psia (1 bar, SCFM reference) and ΔP the allowable pressure drop in psi between the start pressure and the lowest tolerable pressure. The volume comes out in cubic feet.

Should I account for the compressor's make-up flow?

Yes. If the compressor keeps supplying air during the peak, the receiver only has to make up the difference: size on NET flow = demand − make-up. Ignoring make-up oversizes the receiver; if make-up already covers the demand, no buffer receiver is needed for that event.

Does a smaller allowable pressure drop mean a bigger receiver?

Exactly. Volume is inversely proportional to ΔP: tolerating a 5 psi drop instead of 15 psi triples the required volume. The lowest tolerable pressure (below which your equipment drops out) is what sets ΔP.

Let’s talk about your compressed air system

A free consultation to pinpoint your fastest wins.

Free consultation