Sizing a compressed-air buffer (storage) receiver
A buffer receiver stores compressed air to ride through a short demand peak without collapsing network pressure. Its volume is found directly from four inputs — the peak flow, the compressor’s make-up during the peak, the duration, and the pressure drop you can tolerate:
V = (Q_net × t × P_atm) / (60 × ΔP) with Q_net = Q_demand − Q_makeup
| Symbol | Meaning | Unit |
|---|---|---|
| V | Required receiver volume | ft³ |
| Q_net | Net flow the receiver must supply (demand − make-up) | SCFM |
| t | Peak duration | s |
| P_atm | Reference atmospheric pressure ≈ 14.5 psia (1 bar, SCFM reference) | psia |
| ΔP | Allowable pressure drop = start pressure − lowest tolerable pressure | psi |
When do you need a buffer receiver?
The compressor is sized on the average demand; the receiver absorbs the peaks. As soon as a station draws far more than the available capacity for a few seconds — blow-off, long-stroke cylinder, leak test, line start-up — the air must come from a reserve or pressure sags. The receiver decouples supply from demand: it “shaves” the peak and lets the compressor run smoothly.
Net flow: don’t forget the compressor’s make-up
During the peak the compressor doesn’t stop: it keeps feeding the network. So the receiver only has to make up the difference between what the event demands and what the compressor already supplies.
- If make-up ≥ demand, the compressor keeps up on its own: no buffer receiver is needed for that event.
- Otherwise, size on Q_net = Q_demand − Q_makeup. Ignoring make-up gives a needlessly large receiver.
Worked example
A blow-off station draws 100 SCFM for 20 seconds. The compressor supplies 30 SCFM during that time. Pressure starts at 110 psig and must not fall below 95 psig (ΔP = 15 psi).
- Net flow: Q_net = 100 − 30 = 70 SCFM
- V = (70 × 20 × 14.5) / (60 × 15) = 22.6 ft³, i.e. ≈ 169 US gallons (0.64 m³)
So you would pick a dedicated receiver of at least 200 gallons near the station. Ignoring make-up, you would have sized on 100 SCFM (≈ 242 gal) — over 40 % too big.
ΔP is the decisive lever. Volume is inversely proportional to ΔP: if the equipment tolerates only a 5 psi drop (110 → 105) instead of 15, the required receiver triples. The first question to the process is therefore: what is the lowest acceptable pressure?
Local receiver or central receiver
A large central receiver smooths the whole plant; a receiver dedicated to the demanding station (as close to the peak as possible, with its own feed) is often more effective for an isolated, one-off demand. Placement relative to the dryer also matters — see Air receiver: before or after the dryer?.
Flow is reasoned in SCFM; to avoid confusing it with ACFM or standardised units, see Flow units.
With the Onyx M3 tools
- Calculator — Receiver storage — enter the event flow, the compressor make-up, the duration and the two pressures: it computes the net flow and the required volume (gal, ft³, m³).
- Calculator — Metered recovery — goes further: it checks that a given receiver rides through the peak and recharges in time before the next one.
References
- CAGI — Compressed Air & Gas Handbook, Chapter 4 “Compressed Air System Design” — storage and demand management
- Compressed Air Challenge — Best Practices for Compressed Air Systems — storage sizing and peak shaving
- ISO 1217 / CAGI — SCFM reference (1 bar absolute, 20 °C) used as P_atm in the formula