Fundamentals

Sizing compressed-air piping: flow, length, velocity and pressure drop

A line that is too small chokes the flow and drops the pressure; every psi lost in the piping is energy paid to the compressor and then wasted. So a line is sized on two simultaneous criteriaair velocity and pressure drop — from four inputs: flow, length, working pressure and allowable drop.

The four inputs

InputWhat to enterCommon pitfall
FlowThe peak simultaneous flow (SCFM) through the sectionAdding up every tool’s nameplate when they never all run at once
LengthThe developed length of the pipe you will actually install + the equivalent length of fittingsForgetting the fittings; pre-dividing a loop
Working pressureThe real network pressure (psig)
Allowable dropThe pressure drop you accept on this section (psi)Aiming too generously

Flow is given in SCFM (standard cubic feet per minute); see Flow units to convert it correctly and not confuse it with ACFM.

Criterion 1 — air velocity

Lines are first sized on velocity: too fast, the air turns turbulent, noisy, and carries water and debris past the drain legs.

SectionTarget velocityDo not exceed
Main line / header≤ 20 ft/s (6.1 m/s)30 ft/s (9.1 m/s)
Drop / local feed≤ 30 ft/s (9.1 m/s)33 ft/s (10 m/s)

Why these velocities?CAGI (handbook, ch. 4) recommends that velocity in distribution piping not exceed 30 ft/s (9.1 m/s); to keep liquid water from being carried past the drain legs in main distribution lines, it should not exceed 20 ft/s (6.1 m/s). A branch line with a velocity above 33 ft/s (10 m/s) should not exceed 50 ft in length. The British Compressed Air Society (BCAS) holds the same 20 ft/s (6 m/s) benchmark for mains; beyond that you add erosion and noise. Our calculators flag any velocity above an absolute ceiling of 35 ft/s (~10.7 m/s).

Criterion 2 — pressure drop (the deciding criterion)

Velocity is a guardrail, but pressure drop is usually what sets the diameter. CAGI sets the reference rule: pressure drop between the compressor discharge (P2) and the point of use should not exceed 10% of the discharge pressure — and a drop to a station should stay under 1 psi. Network manufacturers aim tighter on distribution alone: ≤ 1.5 psi (0.1 bar) from the compressor to the farthest point of use, hoses and fittings included (Prevost sizes its tables at 116 psi / 8 bar with a 5% loss, i.e. ≈ 5.8 psi / 0.4 bar).

This is energy. CAGI notes that at a nominal 100 psig, every 2 psi change in discharge pressure changes a positive-displacement compressor’s power by about 1%. Lowering the set pressure by 10 psi therefore cuts consumption by about 5%. Undersized piping forces you to raise that set pressure to compensate: you pay for the loss twice.

The filters and the dryer also consume pressure drop: budget them in the total. See line filters and dryers.

Fittings count: the equivalent length

Every elbow, tee or valve behaves like an extra length of straight pipe. Together, fittings add an equivalent length often comparable to that of the straight pipe — so they cannot be ignored.

The method: add an equivalent length per fitting (Le/D ratio). Common values (Crane TP-410): 90° elbow ≈ 30 × D, branch-flow tee ≈ 60 × D; CAGI (handbook ch. 4, table 4.15) publishes these equivalent lengths directly in feet per nominal diameter. The design length becomes: developed length + sum of equivalent lengths. The more elbows and tees a layout has, the larger the diameter required — hence the value of a clean geometry. See Saddle-branch takeoff and Drop and outlet manifold.

Open line or loop: where the length is measured

This is the most confusing point. The rule is simple: always enter the pipe you actually install, then state the topology; the calculation applies the physics.

Open-line network: the length runs from the compressor (point A) to the farthest point of use
Open line — measure the length from the compressor (point A) to the farthest point of use. The full flow travels the entire length.
Loop network: the length is the full developed length of the ring
Loop (closed ring) — enter the full developed length of the ring. Since air feeds each station from both sides, the calculation reduces to ½ length and ½ flow: smaller diameter, steadier pressure.

In an open line, a single run goes from the supply point out to the stations: simple, but the full flow crosses the entire length, giving a larger diameter and a bigger drop at the far end (“air starvation” at distant stations). In a loop, the line returns to the supply point: each station is fed from both sides, so the longest path and the per-branch flow are about halved. The result: a smaller diameter for the same drop, steadier pressure, and the ring acts as buffer storage. As Prevost puts it: looping the system can cut your pressure drop in half, with a minimum of elbows.

Key point — for a loop, enter the full length of the ring (back to the supply point), not half: the tool applies the ÷2 itself. If you fed it the half-length, the network would be undersized.

Material: why aluminium

For the same diameter, a smooth-bore aluminium tube offers less friction than steel. Above all, it does not corrode: the bore stays clean and the diameter is maintained for years, whereas black or galvanised steel scales up (rust shrinks the bore, adds drop and creates leaks, sometimes within months). Its fittings are full-flow, with no restriction, and the network is easy to modify. See the EQOfluids network accessories, the exact tube dimensions (PN16 / PN70) and Pipe supports and fixing.

Installation best practices

  • Oversize slightly for leaks and future expansion: one size up costs little, the pressure-drop saving is permanent.
  • Main line ≥ 2.5 m off the floor, drops terminating around 1.2 m (Prevost).
  • Take air off the top of the main (takeoff over the top) so condensate is not dragged into the drop; a slight slope toward drain points. See Water in the compressed-air system.

With the Onyx M3 tools

  • Network estimator — enter the flow, the actually-installed length and the topology: it sizes the main line AND each drop (on its own tool flow), then builds the bill of materials ready to add to your quote.
  • Calculator — Pipe sizing — compares under / optimal / over diameters by pressure drop and by velocity, open and closed loop. Take the larger of the two (the safer choice).

In both cases: enter the pipe you actually install, pick the topology, and let the tool apply the physics (½ length + ½ flow for a loop).

References

  • CAGI — Compressed Air & Gas Handbook (7th ed., 2021), Chapter 4 “Compressed Air System Design” — distribution velocity ≤ 30 ft/s, main lines ≤ 20 ft/s (water carryover), branch lines > 33 ft/s limited to 50 ft; pressure drop ≤ 10% of discharge pressure; equivalent lengths of fittings (Table 4.15); 2 psi = 1% power rule
  • Crane — Technical Paper No. 410 (TP-410), Flow of Fluids Through Valves, Fittings and Pipe — equivalent lengths (Le/D) of fittings
  • British Compressed Air Society (BCAS) — recommended velocities (20 ft/s main, 30 ft/s drop)
  • Atlas Copco — compressed-air piping sizing (velocity 20–30 ft/s, pressure drop ≤ 1.5 psi / 0.1 bar)
  • PrevostPrevost Piping System, technical documentation (loop = ½ the drop, install heights)
  • EQOfluids — DN20–DN160 aluminium network

Frequently asked questions

What is the maximum air velocity in a compressed-air line?

Per CAGI (handbook, ch. 4), velocity in distribution piping should not exceed 30 ft/s (9.1 m/s); in main lines, aim for ≤ 20 ft/s (6.1 m/s) so water is not carried past the drain legs. A branch line with a velocity above 33 ft/s (10 m/s) should not exceed 50 ft in length. Velocity is a guardrail: pressure drop is usually what sets the diameter.

What pressure drop is acceptable between the compressor and the tool?

CAGI sets the general rule: pressure drop between the compressor discharge (P2) and the point of use should not exceed 10% of the discharge pressure, and a drop to a station should stay under 1 psi. For distribution alone, manufacturers aim tighter, ≈ 1.5 psi (0.1 bar). On the energy side, CAGI notes that at 100 psig every 2 psi increase in discharge pressure costs ~1% in compressor power (positive-displacement).

Why loop the compressed-air network?

In a loop, air reaches each station from both sides of the ring: the per-branch flow and the critical distance are halved. For the same pressure drop you can therefore use a smaller diameter; pressure is steadier and the loop acts as buffer storage. Prevost notes that a looped network can cut pressure drop in half.

Should I oversize the piping?

Slightly, yes. One size up costs little, while the pressure drop it avoids — and the energy that goes with it — is permanent, and it leaves margin for leaks and future expansion. Excessive oversizing, however, adds nothing once velocity and drop are comfortable.

Let’s talk about your compressed air system

A free consultation to pinpoint your fastest wins.

Free consultation