Selection tool

Safety relief valve selector

Enter your compressors’ total flow and the MAWP (PMMP) of the weakest link in the network. The tool recommends the right SRV valve, its set pressure and product code.

Units

1 · Total compressor flow BNQ 3650-900:2013 standard Pressure equipment interconnected by piping without a shut-off valve may be treated as a single piece of equipment for the required relieving-capacity calculation. The flow of all compressors connected to the network is therefore added together.

SCFM

2 · MAWP (PMMP) of the weakest link Weakest link The weakest link can be any element of the network. Review the maximum allowable working pressure (MAWP / PMMP) of each receiver, each fitting and each pipe, then keep the lowest value.

psig

Method — Set pressure rounded down to the nearest 5 psig ≤ MAWP (never above the weakest link). ASME Section XIII capacity = factor × (1.10 × set pressure + 14.7). HP estimate → 5 SCFM/HP. ACFM ≈ SCFM (atmospheric intake). Results to be confirmed.

Awaiting input

Enter the total flow and the MAWP to get a recommendation.